(a) Purpose. The purpose of this article is:
(1) To protect the public potable water supply of the City of Plains, Kansas from pollution or contamination due to cross connection,
(2) To prohibit and eliminate all cross connections within the public potable water supply system and,
(3) To provide for the maintenance of a continuing effective cross connection control program and thus protect the public health.
(b) Responsibility. The Agency shall be responsible for effectively conducting the cross connection control program of the City of Plains, Kansas’s public potable water supply. If in the judgment of said Agency an approved backflow prevention device is required, the Agency or his agent will give notice in writing to the customer to install the proper device. The customer shall immediately install the proper device at the customer’s expense. Failure to comply shall be grounds for discontinuing water service to said customer until the device is properly installed.
(Ord. 493; Code 2013)
(a) Agency. The department of the municipal government or water purveyor invested with the responsibility for enforcement of this article.
(b) Air Gap. The unobstructed vertical distance at least twice the diameter of the supply line and no less than one inch, through the free atmosphere between the lowest opening from any pipe or faucet supplying water to a tank, plumbing fixture, or other device and the flood level rim of the receptacle.
(c) Approved device. Shall mean devices tested and accepted by a recognized testing laboratory approved by the Kansas Department of Health and Environment and the Agency.
(d) Backflow. The flow of water or other substances into the distribution system of a potable supply of water from any source other than its intended source. Backsiphonage is one type of backflow.
(e) Backflow Preventer. A device or means to prevent backflow.
(f) Backsiphonage. The flowing back of contaminated or polluted substances from a plumbing fixture or any vessel or source into the potable water supply system due to negative pressure in said system
(g) Contaminant. Any substance that upon entering the potable water supply would render it a danger to the health or life of the consumer.
(h) Cross Connection. Any physical connection or arrangement between two otherwise separate piping systems, one of which contains potable water and the other which contains water or any substance of unknown or questionable quality whereby there may be flow from one system to the other.
(i) Double Check Valve Assembly. A device consisting of two internally loaded soft seated check valves with positive shut-off valves on both upstream and downstream ends, and properly located test ports.
(j) Dual Check Valve. A device consisting of two internally loaded soft seated check valves. This device does not contain test ports and is acceptable for use only at the meter of residential customers.
(k) Free Water Surface. A water surface at atmospheric pressure.
(l) Flood Level Rim. The edge of the receptacle from which water overflows.
(m) Frost Proof Closet. A hopper with no water in the bowl and with the trap and water supply control valve located below frost line.
(n) KDHE. The Kansas Department of Health and Environment.
(o) Plumbing. The practice, materials and fixtures used in the installation maintenance, extension and alteration of all piping fixtures, appliances and appurtenances.
(p) Pollution. The presence of any foreign substance (organic, inorganic or biological) in water which tends to degrade its quality so as to constitute a hazard or impair the usefulness or quality of the water to a degree which does not create an actual hazard to the public health but which does adversely affect the water.
(q) Reduced Pressure Zone Backflow Preventer. An assembly of two independently acting soft seated approved check valves together with a hydraulically operating mechanically independent differential pressure relief valve located between the check valves and at the same time below the first check valve. The unit shall contain properly located test cocks and resilient seated shut-off valves at each end of the assembly. To be approved these assemblies must be accessible for inspection and testing and be installed in an above ground location where no part of the assembly will be submerged.
(r) Tester. A trained technician certified in the testing and repair of backflow preventers.
(s) Vacuum. Any absolute pressure less than that exerted by the atmosphere.
(t) Vacuum Breaker. A device that permits entrance of air into the water supply distribution line to prevent backsiphonage.
(u) Water, Potable. Water free from impurities in amounts sufficient to cause disease or harmful physiological effects. Its quality shall conform to Kansas Department of Health and Environment requirements for public water supplies.
(v) Water, Non Potable. Water that is not safe for human consumption or that is of questionable potability.
(Ord. 493; Code 2013)
(a) General. A public potable water supply system shall be designed, installed and maintained in such a manner as to prevent contamination from non potable sources through cross connections or any piping connection to the system.
(b) Cross Connections Prohibited. Cross connections are prohibited except when and where as approved by the Agency suitable backflow preventers are properly installed, tested and maintained to insure proper operation on a continuing basis.
(c) Interconnections. Interconnection between two or more public water supplies shall be permitted only with the approval of the Kansas Department of Health and Environment. (K.S.A. 65-163(a))
(d) Individual Water Supplies. Connections between a private water supply and the public potable water are prohibited. (K.S.A. 65-163 (a)).
(e) Connections to Boilers. Potable water connections to boiler feed water systems in which boiler water conditioning chemicals are or can be introduced shall be made through an air gap or through a reduced pressure zone principle backflow preventer located in the potable water line before the point where such chemicals may be introduced.
(f) Prohibited Connections. Connection to the public potable water supply system for the following is prohibited unless properly protected by the appropriate backflow prevention device.
(1) Bidets
(2) Operating, dissecting, embalming, and mortuary tables or similar equipment -- in such installations the hose used for water supply shall terminate at least 12 inches away from every point of the table or attachments.
(3) Pumps for non potable substances. Priming only through an air gap.
(4) Building drains, sewers, or vent systems.
(5) Commercial buildings or industrial plants manufacturing or otherwise using polluting or contaminating substances.
(6) Any fixture of similar hazard.
(g) Refrigeration Unit Condensers and Cooling Jackets. Except when potable water provided for a refrigeration condenser or cooling jacket is entirely outside the piping or tank containing a toxic refrigerant, the inlet connection shall be provided with an approved backflow preventer. Heat exchangers used to heat water for potable use shall be of the double wall type.
(h) Protective Devices Required. The type of protective device required under this article shall be determined by the degree of hazard which exists as follows:
(1) Premises having auxiliary water supply shall protect the public system by either an approved air gap or an assembly.
(2) Premises having water or substances which would be non hazardous to the health and wellbeing of the consumers shall protect the public system with no less than an approved double check valve assembly.
(3) Premises where material dangerous to health is handled in a manner which creates an actual or potential hazard shall protect the public system by an approved air gap or an approved reduced pressure principle backflow prevention assembly.
(4) Premises where cross connections are uncontrolled shall protect the public water supply by installing an approved air gap or an approved reduced pressure principle backflow prevention device at the service connection.
(5) Premises where because of security requirements or other prohibitions it is impossible to complete an in plant cross connection inspection, the public system shall be protected by an approved air gap or an approved reduced pressure principle backflow prevention assembly.
Premises which may fall into one or more of the above mentioned categories may be, but are not limited to the following:
(A) Beverage bottling plants.
(B) Buildings - Hotels, Apartments, Public or private buildings, or other structures having actual or potential cross connections.
(C) Car wash facilities.
(D) Chemical manufacturing, handling, or processing plants.
(E) Chemically contaminated water.
(F) Dairies and cold storage facilities.
(G) Film or photography processing laboratories.
(H) Fire systems.
(I) Hospitals, Medical Centers, Morgues, Mortuaries, Autopsy facilities, Clinics, or Nursing and Convalescent homes.
(J) Irrigation systems.
(K) Laundries.
(L) Metal cleaning, processing, or fabricating plants.
(M) Oil and gas production, storage, or transmission facilities
(N) Packing or food processing plants.
(O) Paper and paper products plants.
(P) Power plants.
(Q) Radioactive materials plants or handling facilities.
(R) Restricted or classified facilities.
(S) Rubber plants.
(T) Sand, Gravel, or Asphalt plants.
(U) Schools or Colleges.
(V) Sewage and storm drainage facilities and reclaimed water systems.
(W) Solar heating systems.
(X) Temporary service - fire hydrants, air valves, blow-offs and other outlets.
(Y) Water front marinas.
(Z) Bulk water loading facilities.
(Ord. 493; Code 2013)
Approved devices shall be installed at all fixtures and equipment where backflow or backsiphonage may occur and where a minimum air gap between the potable water outlet and the fixture or equipment flood-level rim cannot be maintained. Backflow and backsiphonage devices of all types shall be in an accessible location. Installation in pits or any other location not properly drained shall be prohibited, except that dual check valves may be installed in the meter box.
(a) Connections not subject to backpressure. Where a water connection is not subject to back pressure, a vacuum breaker shall be installed on the discharge side of the last valve on the line serving the fixture or equipment. A list of some conditions requiring protective devices of this kind are given in the following table titled Cross Connection Where Protective Devices are Required.
CROSS CONNECTIONS WHERE PROTECTIVE DEVICES ARE REQUIRED AND CRITICAL LEVEL (C-L) SETTINGS FOR VACUUM BREAKERS.
Fixtures or Equipment |
Method of Installation |
Aspirators & ejectors |
C-1 at least 6 inches above flood level of receptacle
served. |
Dental units |
On models without built in vacuum breakers C at least 6
inches above flood level rim of bowl. |
Commercial dish washing machine |
C-L at least 6 inches above flood level of machine.
Installed on both hot and cold water supply lines. |
Garbage can cleaning machines |
C-L at least 6 inches above flood level of machine.
Installed on both hot and cold water supply lines. |
Hose Outlets |
C-1 at least 6 inches above highest point on hose line. |
Commercial laundry machines |
C-L at least 6 inches above flood level of machine.
Installed on both hot and cold water supply lines. |
Lawn sprinklers |
C-L at least 6 inches above highest sprinkler head or
discharge outlet. |
Steam tables |
C-L at least 6 inches above flood level rim. |
Tanks and vats |
C-L at least 6 inches above flood level rim or line. |
Through urinals |
C-L at least 30 inches above perforated flush pet |
Flush tanks |
Equipment with approved ball cock, installed according to
manufacturer’s instructions. |
Hose bibs |
C-L at least 6 inches above flood level of receptacle
served. |
(b) Connections subject to backpressure. Where a potable water connection is made to a line, fixture, tank, vat, pump, or other equipment with a hazard of backflow or backsiphonage where the water connection is subject to backpressure, and an air gap cannot be installed, the Agency may require the use of an approved reduced pressure principle backflow preventer. A partial list of such connections is shown in the following table “Partial List of Cross Connections Subject to Back Pressure”.
Partial List of Cross Connections Subject
to Back Pressure
Chemical lines
Dock water outlets
Individual water supplies
Industrial process water lines
Tanks & vats - bottom inlets
Pumps
Steam lines
Swimming pools
Pressure tanks
Hose bibs
(c) Barometric Loop. Water connections where an actual or potential backsiphonage hazard exists may in lieu of devices specified above be provided with a barometric loop. Barometric loops shall precede the point of connection.
(d) Dual Check Valve. Dual check valves may be installed at the meter. These valves shall be inspected and repaired not less frequent than every year. These valves shall be installed only in situations where the Agency is assured that only noncontaminating substances are subject to backflow into the potable system.
(e) Vacuum Breakers. Atmospheric vacuum breakers shall be installed with the critical level at least six inches above the flood rim of the fixture they serve and on the discharge side of the last control valve to the fixture. No shut off valve or faucet shall be installed beyond the atmospheric vacuum breaker. Pressure vacuum breakers shall be installed with the critical level at least twelve inches above the flood rim but may have control valves downstream from the vacuum breaker. For closed equipment or vessels such as pressure sterilizers the top of the vessel shall be considered the flood level rim and a check valve shall be installed on the discharge side of the pressure vacuum breaker.
(Ord. 493; Code 2013)
15-2a05. Maintenance and repair.
It shall be the responsibility of building and premise owners to maintain all backflow preventers and vacuum breakers with the building or on the premises in good working order and to make sure no piping or other arrangements have been installed for the purpose of bypassing the backflow devices. Testing and repair of these devices should be made by qualified technicians. (Qualified technicians are those technicians who have completed a Kansas Department of Health and Environment approved training course and have passed a writing examination such as the American Backflow Prevention Association device testers examination.) The Agency shall certify the device testers after ascertaining the technician meets the above qualifications. The Agency will also assure the proper installation of all backflow preventers in accordance with the Uniform Plumbing Code, and will set appropriate testing and overhaul schedules for such devices. Testing intervals shall not exceed one (1) year and overhaul intervals shall not exceed three (3) years.
(a) Certified Tester/Repair Technicians. All certified tester/repair technicians shall be re-certified at no less than three year intervals.
15-2a06. Complaints; inquiry and inspection.
The Agency shall make inquiry and inspection of premises upon receiving a complaint or complaints in writing signed by two or more persons stating that it is their belief that a violation of a provision of this article exists, or is informed that a violation of this article may exist by the board of health, chief of police or the fire chief. The Agency may make such inquiry and inspection when such Agency observes conditions which appear to constitute a violation of any provision of this article. Upon making any inquiry and inspection, the Agency shall make a written report of findings.
(a) Whenever necessary to make an inquiry or inspection of any building, structure or premises to determine if a violation of this article exists, the Agency is authorized to enter such building, structure or premises at all reasonable times.
(b) The authority granted to the Agency by subsection (a) of this section is subject to the following:
(1) If the building, structure or premises is occupied, the Agency shall first present proper credentials, explain the purpose for which admittance is desired and demand entry.
(2) If such property is unoccupied, the Agency shall first make a reasonable effort to locate the owner or other person having charge or control of the property, present proper credentials, explain the purpose for which admittance is desired and demand entry.
(3) If the Agency is refused admission or cannot locate the owner or occupant, the Agency shall refrain from entering until authorized to do so by proper judicial authority.
(a) Notification. The Agency shall notify the owner, or authorized agent of the owner, of a building or premises in which there is found a violation of this article, of such violation. The Agency shall set a reasonable time for the owner to have the violation corrected. If the owner fails to correct the violation within the specified time, the City of Plains, Kansas shall cease delivery of water to the building or premises until the violation shall be satisfactorily corrected.
(b) Fines. Should the owner fail to have the violation corrected, the Agency may file a complaint in the Municipal Court of the City against such owner, and upon the conviction of any violation of any of the provisions of this article be fined in an amount not to exceed 30 days, or be both fined and imprisoned.
(Ord. 493; Code 2013)